From: "Stuart, Ralph" <Ralph.Stuart**At_Symbol_Here**keene.edu>
Subject: Re: [DCHAS-L] Vented flammables cabinets
Date: Mon, 29 Jun 2015 17:05:01 +0000
Reply-To: DCHAS-L <DCHAS-L**At_Symbol_Here**MED.CORNELL.EDU>
Message-ID: CFB799DB-E79D-4911-BD1F-1A0D098A392A**At_Symbol_Here**keene.edu
In-Reply-To <5E76EF51D002544DAC5CFA68490FC5DA72AB670A**At_Symbol_Here**CAE145EMBP03.ds.sc.edu>
I think that it‰??s worth mentioning that I‰??ve had experience with properly vented flammable cabinets that the flame arrestors corroded and gummed up within about 5 years of installation and significantly reduced air flow through the hood. The screens were welded into place, so replacing them was not an option.
- Ralph
Ralph Stuart, CIH, CCHO
Chemical Hygiene Officer
Keene State College
ralph.stuart**At_Symbol_Here**keene.edu
Previous post | Top of Page | Next post